REQUIREMENTS:
A normal Serial DB-9 cable 9 PIN is used to connect serial host to the ALEOS gateway.
The serial host behind the gateway needs to be PPP aware and knows how to initiate a PPP connection in order to be able to talk to the gateway (Otherwise serial host will not be able ping gateway and vice versa).
Serial PPP default subnet may be changed:
>> Device PPP IP Sets the device IP address: 192.168.15.31
>> Host PPP IP Sets the host IP address: 192.168.15.100
Port forwarding rule will need to reflect the Host PPP IP address: 192.168.15.100
CONFIGURATION:
ACEmanager: Serial > RS232 Configuration > General > RS232 > RS232 Port = Enable
ACEmanager: Serial > RS232 Configuration > General > RS232 > Startup Mode Default = PPP
ACEmanager: Serial > RS232 Configuration > PPP:
>> Device PPP IP Sets the device IP address: 192.168.15.31
>> Host PPP IP Sets the host IP address: 192.168.15.100
>> Host Authentication Mode = NONE (Can be Modified if needed).
ACEmanager: Security > Port Forwarding > Port Forwarding = Enable
ACEmanager: Security > Port Forwarding > Port Forwarding > Add More and populate the table with the related TCP/UDP listening ports and Serial Host IP.
>> Port forwarding rule will need to reflect the Host PPP IP address: Ex (192.168.15.100)